EXXONMOBIL PIPELINE CO

hazardous_liquid Incident — — February 2, 2011

Incident Information

Incident DateFebruary 2, 2011
OperatorEXXONMOBIL PIPELINE CO
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.88583, -95.41083

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$45,000
Other Costs$0

Location Map

Incident Narrative

"UNKNOWN FLOW SOURCE (SUSPECT PSV BUT UNPROVEN) STARTED RELIEVING TO SUMP DURING DELIVERY OF DIESEL TO NORTH HOUSTON TERMINAL. -SUMP TANK AUTOMATICALLY PUMPED ~150 BBL TO TERMINAL SLOP TANK UNTIL SLOP TANK EHL SHUT DOWN THE SUMP PUMP. -UPON RECEIVING SLOP TANK EHL ALARM THE OCC CONTROLLER COMMANDED THE METER STATION ESD VALVE TO CLOSE. -ESD VALVE (MOTOR-OPERATED GATE VALVE) WAS FROZEN OPEN DUE TO ICE ACCUMULATION ON THE STEM. -ESD VALVE STEM COVER WAS IN PLACE AND IN GOOD CONDITION, BUT MOISTURE HAD ACCUMULATED INSIDE THE COVER. -CONTROLLER SHUT DOWN THE PIPELINE WHEN UNABLE TO CLOSE THE DRAW VALVE. -SUMP TANK OVERFILLED DURING BIPL SHUTDOWN. -DURING TESTING EMPCO WAS UNABLE TO DETERMINE THE SOURSE OF THE FLOW TO THE SUMP. ALL DRAIN VALVES AND PSVS WERE REPLACED."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in