ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — May 4, 2011

Incident Information

Incident DateMay 4, 2011
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates38.04121, -97.40789

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,291
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"A THIRD PARTY CALLED OPERATIONS AT 15:10 ON 5/4/2011 OF A RELEASE AT NEWTON STATION. THE UPSTREAM PUMP STATION PERSONNEL SHUTDOWN THE PIPELINE, AND THE LOCAL AREA TECHNICIAN FOR NEWTON STATION WAS DISPATCHED. SINCE THE RELEASE WAS AT THE PUMP, THE TECHNICIAN BLOCKED IN AND BLEW DOWN THE PUMP PIPING. THE RELEASE WAS DETERMINED TO BE A FAILURE OF THE COOLING TUBING ON THE OUTBOARD PUMP BEARING HOUSING THAT WAS FLOWING PRODUCT AS COOLANT. THE PUMP WAS NOT OPERATING AT THE TIME OF DISCOVERY OF THE RELEASE AND IS CURRENTLY BLOCKED IN, BLOWN DOWN AND TAGGED OUT PENDING REPAIR. THE PIPELINE BYPASSING THE PUMP WAS RESTARTED AT 20:04 ON 5/4/2011."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in