COLONIAL PIPELINE CO

hazardous_liquid Incident —

Incident Information

Report Date
OperatorCOLONIAL PIPELINE CO
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.48354, -80.73570

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ROUTINE STATION CHECK ON 02/25/10 DISCOVERED STAINING IN VICINITY OF UNIT 1 PIPING. EXCAVATED AREA AND DISCOVERED PRODUCT SEEPING FROM TOP FLANGE OF THE CHECK VALVE BETWEEN UNIT 1 SUCTION AND DISCHARGE VALVES. FREE PRODUCT WAS ABSORBED AND CONTAMINATED SOIL EXCAVATED. THE RELEASE IMPACTED SOIL AROUND THE CIRCUMFERENCE OF THE CHECK VALVE APPROXIMATELY 2 FEET OUT AND 3 FEET DEEP. THE EXCAVATED SOIL WAS TRANSPORTED FOR TREATMENT AND DISPOSAL. THERE WERE NO IMPACTS TO SURFACE WATER OR GROUNDWATER. CHECK VALVE WAS PERMANENTLY REPAIRED BY REPLACING O-RING SEAL ON 3/1/10. ONE HALF GALLON OF FREE PRODUCT WAS RECOVERED. APPROXIMATELY 5 CUBIC YARDS OF CONTAMINATED SOIL WAS EXCAVATED. THE EXCAVATED SOIL CALCULATION REVEALED 22.47 GALLONS EQUIVALENT. THE TOTAL AMOUNT IS BELOW THE THRESHOLD FOR NORTH CAROLINA REPORTING REQUIREMENTS.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.