MOBIL CORP

hazardous_liquid Incident — — October 3, 2011

Incident Information

Incident DateOctober 3, 2011
OperatorMOBIL CORP
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates33.84735, -118.31848

Cause

CauseCORROSION FAILURE
SubcauseEXTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$10,000
Emergency Response$5,000
Other Costs$10,000

Location Map

Incident Narrative

"ON 10/3/11, THE TORRANCE REFINERY EXPERIENCED A PINHOLE LEAK NEAR THE TORRANCE METER STATION FOR THE 8"" TRUCK UNLOAD RELIEF PIPELINE. THE LEAK RESULTED IN A 41 BBL LOSS OF PRIMARY CONTAINMENT OF WHICH ALL WAS CONTAINED WITHIN THE CONFINES AND PROPERTY OF THE EXXONMOBIL REFINERY. THIS IS A RELIEF PIPELINE THAT PROTECTS EXXONMOBIL PIPELINE COMPANY COMMODITY PIPELINES WHICH ARE UPSTREAM FROM THE TORRANCE METER STATION. THIS SECTION OF RELIEF PIPING RUNS FROM THE METER STATION TO THE 2 DESIGNATED BREAKOUT TANKS INSIDE THE REFINERY. AS A RESULT OF THE LEAK, THE RELIEF PIPING AND EXXONMOBIL PIPELINE COMMODITY PIPELINES WERE IMMEDIATELY TAKEN OUT OF SERVICE. THERE WAS NOT A PRESSURE SURGE INCIDENT, BUT RATHER, A PINHOLE LEAK HAD DEVELOPED ON THE EXTERNAL RELIEF PIPING THAT RESULTED IN A LOSS OF CONTAINMENT. NOTE: THE CA STATE FIRE MARSHAL'S OFFICE OF PIPELINE SAFETY IS AWARE OF THIS INCIDENT AND A CSFM REPRESENTATIVE VISITED THE SITE TO REVIEW POST INCIDENT, AND REVIEWED THE REQUIRED HYDROTESTING THAT WAS CONDUCTED AS PART OF RECOMMISSIONING OF THE RELIEF PIPELINE. PART E5F UPDATE WAS MADE 1/21/14 BY THAD MASSENGALE, EXXONMOBIL PIPELINE CO."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in