NUSTAR PIPELINE OPERATING PARTNERSHIP L.P.

hazardous_liquid Incident — — March 12, 2012

Incident Information

Incident DateMarch 12, 2012
OperatorNUSTAR PIPELINE OPERATING PARTNERSHIP L.P.
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates40.89481, -85.44050

Cause

CauseINCORRECT OPERATION
Subcause"VALVE LEFT OR PLACED IN WRONG POSITION, BUT NOT RESULTING IN A TANK, VESSEL, OR SUMP/SEPARATOR OVERFLOW OR FACILITY OVERPRESSURE"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$150
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

RELIEF VALVE ACTIVATED DUE TO IMPROPER SETTING (720PSI) WELL BELOW THE MOP (1340PSI). A NEW RELIEF VALVE WITH THE PROPER SETTING WAS INSTALLED AND OPERATIONS RESUMED. REVISED COORDINATES ON 11/30/12 REPORT.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in