COLONIAL PIPELINE CO

hazardous_liquid Incident — — April 10, 2012

Incident Information

Incident DateApril 10, 2012
OperatorCOLONIAL PIPELINE CO
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates32.02821, -89.10162

Cause

CauseEQUIPMENT FAILURE
SubcauseOTHER EQUIPMENT FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,000
Emergency Response$13,372
Other Costs$0

Location Map

Incident Narrative

AT APPROXIMATELY 07:00 ON 4/10/2012 A CONTRACT INSPECTOR AND HIS WORK CREW DISCOVERED PRODUCT ESCAPING FROM THE LINE 1 STATION STEM SEAL LEAK DETECTION BOX. THE CONTRACT INSPECTOR IMMEDIATELY NOTIFIED THE LOCAL TECHNICIAN. TECHNICIAN NOTIFIED CONTROLLER AND LEAD TECHNICIAN AND LEAD TECHNICIAN NOTIFIED OPERATIONS MANAGER AND OPERATIONS MANAGER NOTIFIED GCD DIRECTOR AT 11:42. INVESTIGATION ACTIVITIES DETERMINED THAT THE SOURCE OF PRODUCT WAS THE STEM SEAL OF THE LINE 1 UNIT 2 CHECK VALVE AND THAT THE DISCHARGE PIPING FROM THE LEAK DETECTION BOX COULD NOT KEEP UP WITH THE ESCAPING PRODUCT FLOW DUE TO SOME INTERNAL SLUDGE AND CORROSION WITHIN THE LEAK DETECTION BOX DISCHARGE PIPING. THE PRODUCT LEAKING FROM THE CHECK VALVE STEM SEAL WAS PIPED DIRECTLY TO THE FACILITY SUMP WHILE THE CHECK VALVE STEM SEAL AND THE LEAK DETECTION BOX DISCHARGE PIPING WERE REPAIRED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in