ENTERPRISE CRUDE PIPELINE LLC
hazardous_liquid Incident — — April 25, 2012
Incident Information
| Incident Date | April 25, 2012 |
| Operator | ENTERPRISE CRUDE PIPELINE LLC |
| Commodity | CRUDE OIL |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 34.24437, -97.94858 |
Cause
| Cause | INCORRECT OPERATION |
| Subcause | "VALVE LEFT OR PLACED IN WRONG POSITION, BUT NOT RESULTING IN A TANK, VESSEL, OR SUMP/SEPARATOR OVERFLOW OR FACILITY OVERPRESSURE" |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $2,000 |
| Emergency Response | $0 |
| Other Costs | $0 |
Location Map
Incident Narrative
ENTERPRISE FIELD TECH. FOUND OIL ON THE GROUND AT ADDINGTON STATION. IT WAS DETERMINED THAT DURING A BOOSTER REPLACEMENT AND OPERATIONAL VALVE RE-ALIGNMENT THE DAY BEFORE A VALVE WAS LEFT CLOSED THAT PROVIDES THERMAL RELIEF. THE PSI BUILD UP CAUSED THE FAILURE OF A GASKET ON A PD METER. 15 GALLONS RELEASED IN THE STATION MANIFOLD AREA. ALL OIL CONTAINED TO THE PROPERTY. CREW REPAIRED THE METER AND REPLACED THE GRAVEL.