KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates40.52243, -74.25384

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

A VALVE THAT IS NORMALLY SECURED OPEN TO ALLOW FOR THERMAL EXPANSION WAS CLOSED DURING MAINTENANCE WORK FOR ISOLATION PURPOSES. UPON COMPLETION OF THE WORK THE VALVE WAS NOT RE-SECURED IN THE OPEN POSITION. THIS RESULTED IN THERMAL PRESSURE BUILD UP IN AN ISOLATED SECTION OF TERMINAL PIPING AND CAUSED A FLANGE GASKET TO LEAK.