NUSTAR PIPELINE OPERATING PARTNERSHIP L.P.

hazardous_liquid Incident — — December 12, 2010

Incident Information

Incident DateDecember 12, 2010
OperatorNUSTAR PIPELINE OPERATING PARTNERSHIP L.P.
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates38.34136, -97.66619

Cause

CauseEQUIPMENT FAILURE
SubcauseTHREADED CONNECTION/COUPLING FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$500
Emergency Response$2,000
Other Costs$0

Location Map

Incident Narrative

A HEAVY WALL THREADED FITTING FAILED ON A PUMP CASE PRESSURE LINE. THE FITTING HAS BEEN SENT TO A METALLURGICAL LAB FOR FAILURE ANALYSIS. THE FITTINGS FAILED DUE TO FATIGUE CRACKS THAT DEVELOPED IN THE THREAD ROOTS. THE LIKELY SOURCE OF THE STRESS THAT INITIATED AND PROPAGATED THE FATIGUE CRACKS WAS VIBRATION FROM NEARBY EQUIPMENT.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in