ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 32.77597, -102.95923 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
AN ENTERPRISE TECHNICIAN DISCOVERED A Y-GRADE RELEASE ON THE PUMP CASING. THE PUMP WAS ISOLATED AND PRODUCT WAS EVACUATED. THE NIPPLE WAS REMOVED AND REPLACED WITH A PLUG TO PREVENT FURTHER LEAKS. A VIBRATION STUDY INDICATED THAT ADDITIONAL SUPPORT OR RELOCATION OF THE NIPPLE WAS NEEDED TO PREVENT FURTHER RECURRENCE. OTHER PUMPS WERE REVIEWED FOR SIMILAR OPERATIONAL ENVIRONMENT AND MODIFICATIONS WERE MADE WHERE NEEDED TO REDUCE WEIGHT AND LENGTH OF SMALL BORE CONNECTIONS.