ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates30.45239, -93.46400

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

PIPELINE OPERATIONS TECHNICIAN ARRIVED AT NEWTON STATION ON THURSDAY 06/16/11 AT 13:55 AND FOUND SUB GRADE GASOLINE ON THE GROUND CLOSE TO THE 20 INCH PUMP UNIT. IT IS ESTIMATED THAT 12 BBLS OF PRODUCT LEAK ONTO THE GROUND, NONE OF THE PRODUCT ESCAPED THE PROPERTY. INVESTIGATION FOUND THAT A FLANGE GASKET ON THE INLET SIDE OF THE PUMP DISCHARGE CONTROL VALVE (BURIED) STARTED LEAKING. THE FLANGE GASKET WAS REPLACED AND THE STATION WAS RETURNED TO SERVICE. PRESSURES FOR 30 DAYS, PRIOR TO THE LEAK, WAS REVIEWED BY THE CONTROL CENTER AND FOUND NOT ABNORMAL PRESSURES AT THE PUMP STATION. THE SYSTEM HAD NOT BEEN OVERPRESSURED AND FIND NO OTHER CONTRIBUTING FACTORS TO CAUSE THE GASKET FAILURE. OPERATING PERSONNEL COULD NOT REMEMBER THE LAST TIME ANY WORK HAD BEEN DONE TO THE CONTROL VALVE OR OTHER RELATED AREA. 3-22-2012 - UPDATED FINAL COST - NB 1/2/2014 - FILLED OUT PART E QUESTION 5F. - NHAN TRUONG

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in