"HOLLY ENERGY PARTNERS - OPERATING, L.P."

hazardous_liquid Incident — — January 29, 2013

Incident Information

Incident DateJanuary 29, 2013
Operator"HOLLY ENERGY PARTNERS - OPERATING, L.P."
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates32.81300, -104.06118

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$7,500
Other Costs$0

Location Map

Incident Narrative

"14:00 RELEASE DISCOVERED BY HEP EMPLOYEE, CALLED INTO THE CONTROL CENTER, AND THE CONTROL CENTER SHUTDOWN THE PUMP. 14:05 CONTRACT CREWS WERE DISPATCHED TO HANDLE CLEAN-UP/ SOIL REMEDIATION. 14:15 THE SUCTION AND DISCHARGE LINES WERE ISOLATED (LEAK STOPPED AND CONTAINED) 15:13 REPORTED THE RELEASE TO NRC. 15:53 REPORTED THE RELEASE TO NM PUBLIC REGULATION COMMISSION (MIKE SMITH). 15:40 CONTRACT CREW AND BACKHOE AND ARRIVED ON-SITE. THE FREE PRODUCT DID FLOW ABOUT 50 FT (WEST) OUTSIDE OF THE STATION BUT WAS STILL CONTAINED ON THE HEP ROW. THE EQUIPMENT FAILURE WAS DUE TO IMPROPER REBUILD BY A CONTRACTOR. THE ROD BACKED OFF OF THE CROSSHEAD AND HIT THE LINER CAP. THE LOCKING NUT ON THE ROD/CROSSHEAD CONNECTION WAS NOT TIGHT. THE STATION VAPOR MONITOR DID NOT ALARM DUE TO HIGH WIND. THE PUMP WAS REPAIRED AND OPERATIONAL BY 1/30/2013."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in