MID - VALLEY PIPELINE CO

hazardous_liquid Incident — — July 24, 2011

Incident Information

Incident DateJuly 24, 2011
OperatorMID - VALLEY PIPELINE CO
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates39.03543, -84.69089

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

TWO UNITS WERE RUNNING AT HEBRON STATION. UNIT #4 INBOARD PUMP SEAL FAILED. THE MAGNETROL LIQUID LEVEL CONTROL SHUT THE PUMP DOWN AND CLOSED THE VALVES ON THE PUMP. THE CRUDE OIL WAS CONTAINED IN THE RELEASE TRENCHES GOING TO THE SUMP IN THE PUMP ROOM. EMPLOYEES CLEANED THE TRENCHES & PUMP WITH SORBENT PADS. RE-SUBMITTED ON 3/19/2013 TO INCLUDE PART E5F PER PHMSA REQUEST.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in