SUNOCO PIPELINE L.P.

hazardous_liquid Incident — — May 20, 2013

Incident Information

Incident DateMay 20, 2013
OperatorSUNOCO PIPELINE L.P.
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates39.84110, -75.41770

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$35,000
Other Costs$0

Location Map

Incident Narrative

"A 12 INCH STRAINER LID CLOSURE O-RING FAILED AND LEAKED GASOLINE AT THE TWIN OAKS PUMP STATION. THE STRAINER LEAK WAS DISCOVERED BY AN EMPLOYEE. GASOLINE WAS OBSERVED DRIPPING FROM A 12 INCH STRAINER CONFIGURED WITH A METER RUN ON THE 8"" TWIN-ICED PIPELINE. THE PIPELINE WAS SHUT DOWN. IMMEDIATE MEASURES WERE TAKEN TO CONTROL AND CONTAIN THE LEAK. COMPANY PERSONNEL AND CONTRACT OSRO EMERGENCY RESPONDERS WERE ORGANIZED TO ADDRESS THE CLEAN-UP EFFORT FOLLOWING INCIDENT COMMAND STRUCTURE. AN NRC REPORT # 1047704 WAS MADE BECAUSE SHEEN ON WATER WAS DISCOVERED. UPON OPENING THE STRAINER, IT WAS DETERMINED THAT THE STRAINER CLOSURE O-RING HAD FAILED. IMMEDIATE CAUSE OF THE O-RING FAILURE WAS SEAM SEPARATION."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in