"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — June 15, 2013

Incident Information

Incident DateJune 15, 2013
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.73064, -95.20349

Cause

CauseINCORRECT OPERATION
Subcause"TANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$500
Other Costs$0

Location Map

Incident Narrative

"TERMINAL OPERATOR WAS SENT TO FIELD TO PERFORM LINE UP OF STRIPPING OF OUTBOUND PIPING. 2ND OPERATOR WAS SENT TO DUAL VERIFY LINE UP FOR THE LINE STRIPPING OPERATION. OPERATOR WHO WAS SENT TO DUAL VERIFY THE LINE UP OPENED AN ADDITIONAL VALVE THAT SHOULD NOT HAVE BEEN OPENED WHICH ALLOWED PRODUCT TO FLOW TO THE BLOWDOWN TANK. FIRST OPERATOR WHO WAS AUTHORIZED TO MAKE THE LINE UP OPENED THE INCORRECT VALVE AT BLOWDOWN TANK. IF HE HAD OPENED THE CORRECT VALVE, A CHECK VALVE WOULD HAVE PREVENTED THE BACK FLOW INTO THE BLOWDOWN TANK. DRUG AND ALCOHOL TESTING TOOK PLACE."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in