ONEOK NGL PIPELINE, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorONEOK NGL PIPELINE, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates36.17115, -97.43226

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ONEOK ORLANDO PUMP STATION SHUTDOWN DUE TO GAS DETECT ALARM. STATION WAS ISOLATED FROM PIPELINE. ONEOK PIPELINE CONTROL CENTER CALLED FIELD REP TO INVESTIGATE SHUTDOWN. ONEOK FIELD REP ARRIVED ON LOCATION AT APPROXIMATELY 22:30 AND DISCOVERED A 1"" PIPE NIPPLE ON PUMP HEADER HAD CRACKED AND WAS LEAKING VAPORS. PUMP HEADER WAS DEPRESSURED AND NIPPLE WAS REPLACED. PUMP STATION WAS RESTARTED. INVESTIGATION DETERMINED VIBRATION FROM CONTROL VALVE ON HEADER MAY HAVE LEAD TO NIPPLE FAILURE. CONTROL VALVE WAS REPROGRAMMED AND VIBRATION WAS ELIMINATED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.