COLONIAL PIPELINE CO

hazardous_liquid Incident —

Incident Information

Report Date
OperatorCOLONIAL PIPELINE CO
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates40.57704, -74.24980

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON SEPTEMBER 6, 2012 AT 0416 HRS OPERATOR DISCOVERED LEAKING TWIN-SEAL VALVE PLATE WHILE DOING EQUIPMENT INSPECTION/ROUTINE ROUNDS. OPERATIONS IMMEDIATELY SHUTDOWN AND DEPRESSURED LINE AND CALLED LINDEN JUNCTION LEAD OPERATOR. THE LEAK AT THAT POINT HAD STOPPED. THE LEAD OPERATOR CALLED THE NJ DEP AT 0423 HRS. AND REPORTED LEAK OF ABOUT 40 GALLONS. FINAL ACTUAL LEAK AMOUNT WAS 16 GALLONS. THE VALVE WAS DRAINED OF PRODUCT AND PLATE REMOVED. THE OLD GASKET WAS REMOVED AND SEALING SURFACED CLEANED. A NEW TYPE OF GASKET INSTALLED AFTER APPROVAL BY ENGINEERING. VALVE FLANGE TIGHTENED AND VALVE PUT BACK INTO SERVICE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in