SFPP, LP
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | SFPP, LP |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 33.84494, -118.23243 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
AT APPROX 0935 ON 10/15, DURING A WALK-THOUGH OF THE FACILITY, THE ASSISTANT MANAGER DISCOVERED DIESEL FUEL SPRAYING OUT OF THE BACK OF A MAGNAHELIC GAUGE ON THE VAPOR RECOVERY PIPING ON TANK W-11. THE GAUGE WAS ISOLATED BY CLOSING A BALL VALVE ON THE PIPING ASSOCIATED WITH THE GAUGE. AGENCY SPILL NOTIFICATIONS WERE COMPLETED, AND THE OSRO RESPONDED FOR THE CLEANUP. SPILL VOLUME WAS ESTIMATED TO BE 282 GALLONS. SUBSEQUENT INVESTIGATION FOUND THAT DIESEL FUEL WAS NOT COMPATIBLE WITH THE SILICONE DIAPHRAGM OF THE MAGNAHELIC GAGE CAUSING FAILURE OF THE DIAPHRAGM ALLOWING THE DIESEL TO EXIT THE LOW PORT ON THE BACK OF THE GAGE.