ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 32.11386, -101.25514 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
AT 20:44 CST PIPELINE CONTROL RECEIVED FIRE DETECTION, THEN A HAZARDOUS GAS ALARM REMOTELY. AT 21:20 CST A LOCAL AREA TECHNICIAN ARRIVED AND CONFIRMED A SMALL FLASH FIRE HAD OCCURRED ON FORSAN STATION, TURBINE #4 OPERATING ON THE SEMINOLE RED MAINLINE (LID 50). THE FIRE WAS OUT PRIOR TO THE TECHNICIAN'S ARRIVAL. THERE WAS MINOR DAMAGE TO HORIZONTAL PUMP WIRING AND CONDUITS. INVESTIGATION OF THE ACCIDENT DETERMINED THE LOSS OF INBOARD AND OUTBOARD PUMP SEALS RESULTED IN THE RELEASE OF NATURAL GASOLINE WHICH IGNITED DUE TO THE HIGH TEMPERATURE OF THE GAS TURBINE DRIVER. THE LOSS OF SEAL INTEGRITY WAS DUE TO A REDUCTION IN SEAL FLUSH FLOW DUE TO BUILD-UP OF SEDIMENTS FROM THE PIPELINE.