SHELL PIPELINE CO., L.P.
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | SHELL PIPELINE CO., L.P. |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 30.15735, -93.04560 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
INSULATING GASKET ON THE DOWNSTREAM SIDE OF A MAINLINE BLOCK VALVE AT IOWA PUMP STATION BEGAN LEAKING FOLLOWING THE CONNECTION OF A BYPASS LINE JUST DOWNSTREAM OF THE BLOCK VALVE. THE LEAK WAS FIRST NOTICED AS SMALL ENOUGH TO TIGHTEN THE FLANGE STUDS AND NUTS WHICH STOPPED THE RELEASE FOR OVER ONE HOUR. THE RELEASE BEGAN AGAIN. THE PIPELINE WAS SEGMENTED BY CLOSING OTHER MAINLINE BLOCK VALVE WHICH ISOLATED A 7 MILE LONG SEGMENT OF PIPELINE WHILE ETHYLENE PIPELINE WAS SHUT DOWN. THE ISOLATED SEGMENT WAS BLOWN DOWN THROUGH SEVERAL FLARES. THE FLANGE GASKET CONTINUED TO LEAK UNTIL THE PRESSURE DROPPED TO APPROX. 550 PSI. AT WHICH TIME IT STOPPED. THE ISOLATED PIPELINE SEGMENT CONTINUED TO BE BLOWN DOWN UNTIL IT WAS SAFE TO REMOVE AND REPLACE THE GASKET. THE GASKET WAS REPLACED ON 12/8 AND RESTARTED ON 12/9. THE GASKET WAS A MICARTA INSULATING GASKET USED TO ISOLATE THE PIPELINE SEGMENTS. THIS TYPE OF INSULATING GASKET WAS COMMONLY UTILIZED. IT WAS FOUND TO BE IN GOOD CONDITION. AN INVESTIGATION DETERMINED THE CAUSE OF THE RELEASE WAS DUE TO THE LOSS OF SUPPORT OF THE ABOVEGROUND FLANGE SET WHILE CONNECTING THE TEMPORARY BYPASS PIPING DOWNSTREAM OF THE FLANGE SET. 3/13/2013 - VERIFIED E5F PER REQUEST FROM PHMSA. 11/12/13 - SPOKE WITH BLAINE KEENER, PHMSA - REQUESTED THE RECOVERED VOLUME BE REMOVED FOR THE AMOUNT OF THE INTENTIONAL VOLUME.
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.