"MAGELLAN PIPELINE COMPANY, LP"
hazardous_liquid Incident — — May 1, 2014
Incident Information
| Incident Date | May 1, 2014 |
| Operator | "MAGELLAN PIPELINE COMPANY, LP" |
| Commodity | REFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 35.46577, -97.44754 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | THREADED CONNECTION/COUPLING FAILURE |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $100 |
| Emergency Response | $100 |
| Other Costs | $0 |
Location Map
Incident Narrative
PUMP VIBRATION RESULTED IN THREADED FITTING ON THE DISCHARGE OF THE PUMP CONNECTING TO THE PIPE TO CRACK. THE SECTION OF PIPE WAS REPLACED. A PROJECT PLAN IS IN PLACE TO GROUT IN THE PUMP AND ADD ADDITIONAL SUPPORTS AND IS SCHEDULED FOR 1ST QUARTER 2015.