SFPP, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSFPP, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates38.00366, -122.05622

Cause

CauseMATERIAL FAILURE OF PIPE OR WELD
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT 1242, 8/8/13, DURING A STATION WALK-AROUND INSPECTION, THE OPERATOR NOTICED A VISUAL INDICATION FROM THE TANK LEAK SENSOR SYSTEM AT BREAKOUT TANK CC 9. THERE WAS ALSO A NOTICEABLE ODOR OF GASOLINE NEAR THE TANK, BUT NO STAINING. THREATENED RELEASE NOTIFICATIONS WERE MADE AND LOCAL OPERATIONS BEGAN EMPTYING THE TANK. AT 1404, WHILE SWABBING THE SENSOR TUBE, IT WAS DISCOVERED THAT THE CABLES WERE WET WITH PRODUCT AND INDICATED 100% LEL. FOLLOW-UP RELEASE NOTIFICATIONS WERE MADE AND THE TANK WAS EMPTIED BY 1700 THAT AFTERNOON. SUBSEQUENT INVESTIGATION FOUND A LAP-SEAM WELD CRACKED MOST LIKELY DUE TO FILLING/EMPTYING OF THIS DRAIN-DRY STYLE BREAKOUT TANK. 'NOTE: PART A, #6. ORIGINAL NRC 'THREATENED RELEASE' NOTIFICATION REPORT #1056503 MADE @ 1304, FOLLOW-UP NRC REPORT #1056510 MADE AT 1415 CONFIRMING THE RELEASE. 'NOTE: PART A, #9. WE RECOVERED 1.36 BBLS AND DO NOT KNOW IF THE ENTIRE AMOUNT WAS RECOVERED BECAUSE THE LOCATION OF THE RELEASE WAS UNDER THE TANK. THE SITE IS UNDER A CURRENT RWQCB ORDER AND THIS RELEASE IS BEING INVESTIGATED BY THAT AGENCY THEREFORE, IF A BETTER ESTIMATE IS ATTAINED IN THE FUTURE, WE WILL SUPPLEMENT THIS REPORT. 'NOTE: PART E, #6. TANK LEAK DETECTION SYSTEM IS NOT ASSOCIATED WITH THE SCADA SYSTEM.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in