SUNOCO PIPELINE L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSUNOCO PIPELINE L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.62560, -98.80710

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON APRIL 2, 2014, A TECHNICIAN WAS FILLING THE SUMP AT ZEPHYR STATION IN ORDER TO COMPLETE DOT CALIBRATIONS AND CHECKS ON THE SUMP ALARMS. THE SUMP TANK BECAME OVERFILLED WHEN THE BALL VALVE THE TECHNICIAN WAS USING TO FILL THE SUMP MALFUNCTIONED AND WAS UNABLE TO BE CLOSED TO STOP THE FLOW OF CRUDE TO THE SUMP. THE PIPELINE WAS SHUT DOWN. THE MALFUNCTIONING VALVE WAS SUBSEQUENTLY REMOVED AND REPLACED AND THE MAINLINE WAS RESTARTED. THROUGH INVESTIGATION AND EXAMINATION OF THE REMOVED FAULTY BALL VALVE; IT WAS FOUND THAT THE INTERNAL SEAL OF THE BALL VALVE BROKE AND BECAME LODGED IN THE BODY OF THE VALVE, PREVENTING IT FROM FULLY CLOSING. ALL CONTAMINATED SOIL WAS REMOVED FROM THE AREA AND REMEDIATED ON SITE.