ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates30.01081, -94.05636

Cause

CauseOTHER ACCIDENT CAUSE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 4/17/2014, A FLASH FIRE OCCURRED DURING A PIPELINE TIE-IN INTO AN EXISTING PIPE AT THE BEAUMONT TERMINAL. PRIOR TO COMMENCING WORK, A JOB PLAN WAS DEVELOPED TO ISOLATE AND DRAIN UP THE PIPE HEADER AND PERFORM ATMOSPHERIC MONITORING OF THE WORK AREA. THE EXISTING PIPE WAS THEN COLD CUT AND PURGED OF HYDROCARBONS TO FACILITATE THE TIE-IN OF THE NEW PIPELINE. AIR MOVERS WERE INSTALLED TO PULL ANY POTENTIAL HYDROCARBON VAPORS FROM THE WORK AREA. A FIRE WATCHMAN WAS POSTED AND A ZERO LEL CONDITION WAS ACHIEVED PRIOR TO COMMENCEMENT OF HOT WORK ACTIVITIES. DURING THE TIE-IN WELDING PROCESS, VAPORS ENTERED THE WORK AREA DUE TO INADEQUATE ISOLATION OF THE SEGMENT AND A FLASH OCCURRED. THE WORK SITE WAS SHUT DOWN IMMEDIATELY; THERE WERE NO INJURIES OR PROPERTY DAMAGE. TELEPHONIC NOTIFICATION TO THE NRC WAS MADE DUE TO THE FACT THAT A FIRE OCCURRED. NRC REPORT # 108003 WAS GENERATED. SUBSEQUENT INVESTIGATION WAS CONDUCTED THROUGH CPF 4-2014-5017 AND SUBMITTED TO PHMSA ON JULY 13, 2015.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in