"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — September 9, 2015

Incident Information

Incident DateSeptember 9, 2015
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72536, -95.20334

Cause

CauseOTHER OUTSIDE FORCE DAMAGE
SubcauseELECTRICAL ARCING FROM OTHER EQUIPMENT OR FACILITY

Casualties

Fatalities0
Injuries0

Costs

Property Damage$100,000
Emergency Response$173,000
Other Costs$80,000

Location Map

Incident Narrative

"ON 9-9-2015, SEVERE WEATHER CAUSED A CENTER POINT HIGH VOLTAGE LINE CROSS MEMBER TO FALL, DRAPING LINES OVER A HIGH VOLTAGE 12.47 KV THREE PHASE DISTRIBUTION LINE. THE ELECTRICAL ENERGY FROM THE LIGHTNING WAS TRANSFERRED THROUGH THE POLES STEEL GUIDE WIRE AND INTO THE GROUND WHERE IT ARCED TO THE LCRC 12"" PIPELINE. THIS ARC CAUSED A SMALL HOLE IN THE PIPE THAT CAUSED THE LEAK. UPON DISCOVERY THE LINE WAS SHUT DOWN AND A HARD BOOM PLACED TO CONTAIN THE PRODUCT. REPAIRS WERE COMPLETED ON 9-11-2015."