PHILLIPS 66 PIPELINE LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorPHILLIPS 66 PIPELINE LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.71930, -101.35303

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

THE GOLD LINE 4-WAY PROVER VALVE (AT THE BORGER PRODUCT TERMINAL) HAD A STEM PACKING SEAL LEAK. WHEN THE LEAK WAS DISCOVERED, CATCH PANS WERE PLACED UNDER THE LEAK AND THE PROVER WAS BYPASSED. 12 GALS OF GASOLINE WAS RECOVERED IN THE CATCH PANS AND 2.5 GALS WAS SPILLED TO THE SOIL (AND LATER REMOVED). THE VALVE STEM WAS REPAIRED AND NEW PACKING WAS INSTALLED. THIS VALVE WAS REBUILD IN 2009 (5 YEARS AGO), SO TO PREVENT REOCCURANCE A PREVENTATIVE MAINTENANCE TASK WAS ESTABLISHED IN THE MAINTENANCE MANAGEMENT SYSTEM TO DISASSEMBLE AN INSPECT THE VALVE AT THREE YEAR INTERVALS. THIS SUPPLEMENTAL REPORT IS BEING SUBMITTED TO CORRECT THE ORIGINAL 7000.1 REPORT WHICH INCORRECTLY SPECIFIED THIS EQUIPMENT AS BEING ""INTRASTATE"". THE EQUIPMENT IS ACTUALLY ON A ""INTERSTATE"" PIPELINE, SO THIS WAS FIXED ON THIS SUPPLEMENTAL REPORT. THIS REPORT ASKED FOR ADDITIONAL INFORMATION TO BE PROVIDED VS THE ORIGINAL REPORT. SO THE REQUIRED ADDITIONAL INFORMATION WAS ADDED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in