ENTERPRISE CRUDE PIPELINE LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE CRUDE PIPELINE LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates28.94945, -95.43075

Cause

CauseNATURAL FORCE DAMAGE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT APPROXIMATELY 0901, PIPELINE CONTROL RECEIVED A FIRE SHUTDOWN ALARM FROM ITS JONES CREEK STATION. ENTERPRISE PERSONNEL RESPONDED AND ARRIVED ON SITE AT 0929 TO CONFIRM THE ALARM. IT WAS DETERMINED THAT A LIGHTNING STRIKE HAD IGNITED VAPORS COMING FROM THE SUMP VENT STACK. THE FIRE BURNED ITSELF OUT WITH NO INJURIES OR DAMAGES OCCURRING. THE NRC WAS NOTIFIED DUE TO A FIRE NOT INTENTIONALLY SET BY THE OPERATOR (NRC #1093719). THE VENT STACK DESIGN IS BEING REVIEWED TO DETERMINE THE NEED FOR A FLAME ARRESTER OR ANOTHER ENGINEERED SOLUTION. LOCAL CATCH BASIN DRAIN VALVES WILL BE MONITORED AND CLOSED DURING RAIN EVENTS TO PREVENT POTENTIAL OVER FLOW OF PRODUCT PUSHING VAPORS OUT OF VENT STACK. FLAME SCREENS HAVE BEEN ADDED TO ALL SUMPS AT THIS LOCATION TO PREVENT REOCCURRENCE.