ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — November 14, 2015

Incident Information

Incident DateNovember 14, 2015
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates30.03003, -94.04120

Cause

CauseINCORRECT OPERATION
SubcauseEQUIPMENT NOT INSTALLED PROPERLY

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"OPERATORS PERFORMED MAINTENANCE ON THE VERTICAL STRAINER BASKETS ON THE METER SKID AND RETURNED THE SKID TO OPERATION. THE STRAINER'S SAFETY BLEED VALVE PLUG WAS NOT RE-INSTALLED PRIOR TO THE RETURN OF EQUIPMENT TO OPERATION. WHEN A MOVEMENT OF GASOLINE WAS MADE ON THE METER SKID, APPROXIMATELY 57 GALLONS OF GASOLINE WAS RELEASED FROM THE TWO 1/16"" ORIFICES ON THE SAFETY BLEED VALVE. THE PIPELINE WAS THEN SHUT DOWN AND ISOLATED. RELEASED PRODUCT WAS REMEDIATED, THE PLUG REINSTALLED, THE EQUIPMENT LEAK TESTED, AND THE SKID BROUGHT BACK INTO SERVICE. AN EQUIPMENT-SPECIFIC MAINTENANCE PROCEDURE WAS WRITTEN TO PREVENT REOCCURRENCE OF THIS RELEASE."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in