PLAINS MARKETING, L.P.

hazardous_liquid Incident — — November 18, 2014

Incident Information

Incident DateNovember 18, 2014
OperatorPLAINS MARKETING, L.P.
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates35.93667, -96.74522

Cause

CauseEQUIPMENT FAILURE
SubcauseTHREADED CONNECTION/COUPLING FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$5,000
Emergency Response$10,000
Other Costs$0

Location Map

Incident Narrative

APPROXIMATELY 1 BBL OF CRUDE OIL WAS RELEASED WHEN A SWIVEL JOINT ON THE ROOF DRAIN SYSTEM LOCKED UP, CAUSING STRESS TO BE PLACED ON AN ADJOINING 90-DEGREE FITTING. THE STRESS CAUSED THE FITTING TO CRACK. THE TANK WAS REMOVED FROM SERVICE, THE SWIVEL JOINT AND 90-DEGREE FITTING WERE REPLACED, AND THE TANK WAS PLACED BACK INTO SERVICE. SUPPLEMENTAL NARRATIVE: PER THE PHMSA INSPECTOR'S REQUEST, PART C; ITEMS 3J, 4, 5, PART D; ITEMS 1- 4, PART E; 1-4 AND 6-9 AND PART G; G6; IF OTHER EQUIPMENT FAILURE: ITEMS 5-DESCRIBE: AND 6 HAVE ALL BEEN UPDATED. THIS LEAK WAS A RESULT OF A MANUFACTURING DEFECT ON THE SWIVEL JOINT, IN WHICH IT WAS NOT GREASED PROPERLY, CAUSING IT TO LOCK UP. THE MOST RECENT INSPECTION FOR THE TANK WAS IN 2006. WHEN A TANK IS TAKEN OUT OF SERVICE FOR AN API 653 INTERNAL INSPECTION, IF DEEMED NECESSARY BY THE INSPECTORS, THE ROOF DRAIN WILL BE PRESSURE TESTED AND/OR REPLACED, DEPENDING ON THE AGE OF THE ROOF DRAIN. THE ROOF DRAIN IS THOROUGHLY INSPECTED ALONG WITH OTHER TANK APPURTENANCES DURING THE INSPECTION PROCESS.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in