KINDER MORGAN COCHIN LLC

hazardous_liquid Incident — — December 9, 2014

Incident Information

Incident DateDecember 9, 2014
OperatorKINDER MORGAN COCHIN LLC
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates46.37078, -97.46756

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,500
Emergency Response$5,170
Other Costs$0

Location Map

Incident Narrative

A 0.5 INCH OD AUSTENITIC STAINLESS STEEL SEAMLESS TUBING FROM THE LISBON PUMP STATION FRACTURED AT A CONNECTION TO THE PUMP'S INBOARD SEAL. THE FRACTURE WAS CAUSED BY HIGH CYCLE FATIGUE THAT INITIATED AT A LONGITUDINAL CORROSION CHANNEL INSIDE THE TUBING. THE CORROSION CHANNEL IS APPARENTLY RESULTED FROM ACID USED TO CLEAN AND PASSIVATE THE TUBING DURING THE MANUFACTURING PROCESS. THE TUBING WAS REPLACED WITH NEW TUBING AND TUBING SUPPORTS WERE INSTALLED. 10/1/2015 UPDATE: UPDATED COSTS UNDER PART D FOR EMERGENCY RESPONSE AND ENVIRONMENTAL REMIDIATION.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in