WILLIAMS FIELD SERVICES

hazardous_liquid Incident — — December 24, 2014

Incident Information

Incident DateDecember 24, 2014
OperatorWILLIAMS FIELD SERVICES
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates40.26271, -80.26411

Cause

CauseEQUIPMENT FAILURE
SubcauseMALFUNCTION OF CONTROL/RELIEF EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,000,000
Emergency Response$10,000
Other Costs$0

Location Map

Incident Narrative

ON THE NIGHT OF 12/24 SEVERE WEATHER IN SOUTHWESTERN PA CAUSED INTERMITTENT POWER OUTAGES TO THE HOUSTON PA SITE. THESE RESULTED IN THE LOSS OF PHASE CONVERTERS (DEVICES THAT CONVERT SINGLE PHASE AC POWER TO THREE-PHASE AC POWER) TO THE FACILITY, AND THE SUBSEQUENT LOSS OF INSTRUMENT AIR. THROUGH A NUMBER OF DESIGN FAILURES THIS LOSS OF INSTRUMENT AIR PRESSURE RESULTED IN AN OVERPRESSURE EVENT THAT RESULTED IN THERMAL RELIEF VALVES, CONNECTED TO THE FACILITY MAINTENANCE FLARE SYSTEM, RELIEVING AT MAXIMUM CAPACITY. IN SHORT ORDER THIS RELIEF CASE, WHICH THE FLARE WAS NOT SIZED FOR (BLOCKED CLOSED OVERPRESSURE CASES WERE ASSUMED BE HANDLED BY OTHER MEANS, SLAM VALVES ETC.), RESULTED IN FLARING IN EXCESS OF FLARE DESIGN, FLARE HEADER OVERPRESSURE, AND THE RUPTURE OF THE ETHANE VAPORIZER AT ITS INLET NOZZLE. THIS RUPTURE RELEASED ADDITIONAL FUEL INTO FLARE AREA, WHICH IGNITED FROM THE FLARE, AND FORMED A JET FIRE. THE INCIDENT CONCLUDED AFTER WILLIAMS PERSONNEL ISOLATED SOURCES OF FUEL TO THE FLARE HEADER.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in