ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates27.79952, -97.56450

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 12/30/2014, MAINTENANCE PERSONNEL WERE PREPARING TO REPLACE A VALVE USING A STOPPLE AND A BLOCK VALVE. WHILE THE WORK WAS BEING PERFORMED, THE STOPPLE SEALING ELEMENT HAD DEVELOPED A SMALL LEAK. DURING THE PROCESS OF RETRACTING THE STOPPLE SEALING ELEMENT FOR REPLACEMENT, THE INSULATION FLANGE GASKET ON THE VALVE BEING REPLACED FAILED BEFORE THE SECOND SEALING ELEMENT WAS INSERTED. THE AFFECTED PIPE SEGMENT WAS ISOLATED AND BLOWN DOWN. THE VALVE INITIALLY BEING REPLACED WAS REMOVED AND REPLACED WITH A NEW VALVE AND NEW INSULATION GASKET. THE INSULATION GASKET WAS NEAR ITS LIFE EXPECTANCY. GASKET AGE COMBINED WITH THE MAINTENANCE WORK RESULTED IN ITS FAILURE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in