WILLIAMS FIELD SERVICES

hazardous_liquid Incident — — February 11, 2015

Incident Information

Incident DateFebruary 11, 2015
OperatorWILLIAMS FIELD SERVICES
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates40.26271, -80.26411

Cause

CauseINCORRECT OPERATION
SubcausePIPELINE OR EQUIPMENT OVERPRESSURED

Casualties

Fatalities0
Injuries0

Costs

Property Damage$10,000
Emergency Response$10,000
Other Costs$0

Location Map

Incident Narrative

HOUSTON METER STATION HAD BEEN SHUT DOWN AND WILLIAMS WAS CHANGING OUT A SOLENOID ON OUR VALVE. PIPELINE CONTROL OPENED THE INLET VALVE TO THE STATION THERE WAS AN OVERPRESSURE SURGE AND THE GASKETS ON THE FILTER VESSEL FAILED, THE PSV'S LIFTED AND ETHANE RELEASED BUT LIMITED TO THE FACILITY. OVERPRESSURE WAS DETECTED BY STATION AND THE ESD TRIPPED. THERE WAS NO UNINTENTIONAL FIRE, NO INJURIES, AND A FEW PRECAUTIONARY EVACUATIONS.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in