MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates42.53632, -96.35816

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

BREAKOUT TANK 1334 WAS TAKEN OUT OF SERVICE SO THE TANK GAUGE COULD BE REPAIRED. DURING LOCKOUT/TAGOUT OF THE TANK, A LOCATION OPERATOR CLOSED THE PUMP BYPASS VALVE BACK TO THE TANK AND FAILED TO RECOGNIZE THAT THIS VALVE WAS THE POINT OF THERMAL RELIEF FOR THE RECEIVE LINE AND THE TRUCK LOADING RACK LINE BACK TO THE TANK. WHILE THE BYPASS VALVE WAS CLOSED, THE SECTIONS OF PIPE OVER-PRESSURED AND CAUSED FLANGE LEAKS. DURING THE ENSUING INVESTIGATION ALL GASKETS ON PIPING THAT COULD HAVE BEEN AFFECTED BY THE PRESSURE BUILD UP WERE REPLACED ALONG WITH THE ASSOCIATED BOLTS AND NUTS. APPROXIMATELY 2 CUBIC YARDS OF IMPACTED SOIL WAS REMEDIATED. NOTE"" THE HIGHEST PRESSURE REACHED DURING THE EVENT IS UNKNOWN, AND THE 303 PSIG NUMBER RECORDED IN PART E1 IS AN ESTIMATED ASSUMING THAT THE SYSTEM EXCEEDED 110%.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in