SHELL PIPELINE CO., L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSHELL PIPELINE CO., L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.62187, -90.68984

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

TANK WAS TAKEN OUT OF SERVICE TO PERFORM ROUTINE MAINTENANCE. THE HEADER PIPING TO THE TANK WAS ISOLATED AND NO THERMAL RELIEF WAS PROVIDED. FLANGE GASKET INVOLVED IN RELEASE WAS REPLACED AND TEMPORARY THERMAL RELIEF WAS INSTALLED WHILE MAINTENANCE WAS CONDUCTED. A PLAN TO PROVIDE PERMENANT THERMAL RELIEF IS UNDERWAY. THE PERMIT TO WORK DID NOT CAPTURE THE RISK OF THERMAL RELIEF WITHIN THE THE PTW PROCESS. RELIABILITY AND INTEGRITY TEAM UPDATED THE MECH. I&M MANUAL SECT. 3.11 TO IMPROVE ISOLATION OF EQUIPMENT. MAINT. AND OPS WERE TRAINED OF UPDATE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in