MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.79733, -95.27870

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON APRIL 25, 2015 TANK 3512 AND 3513 HAD TANK MIXER SEAL FAILURES (ONE MIXER PER TANK). THE SEAL FAILURES RESULTED IN 10 BBLS OF CRUDE OIL (WTI) BEING RELEASED FROM THE TWO TANKS. THE CRUDE OIL WAS RELEASED TO THE TANK DIKE CONTAINMENT AND TANKS REMAINED OUT OF SERVICE UNTIL REPAIRS COULD BE COMPLETED. JENSEN MIXERS INTERNATIONAL PERFORMED AN ANALYSIS OF THE SEAL FAILURES AND DETERMINED THE CAUSE OF THE FAILURE TO BE SOLID MATERIAL FROM THE CRUDE ENTERED THE SEAL AND CAUSING ABRASION. ALONG WITH THE ABRASION, POTENTIALLY UPON RESTART OF THE MIXERS, THE FOREIGN MATERIAL CREATED ENOUGH FRICTION THAT CAUSED A FAILURE OF THE CARBON COMPONENTS. THE SEALS WERE REPLACED WITH BRONZE/TUNGSTEN COMPONENTS TO IMPROVE WEAR AND PREVENT FUTURE FAILURES.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in