SHELL PIPELINE CO., L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSHELL PIPELINE CO., L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates37.72166, -121.54831

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

THE CONTROL CENTER COMMANDED THE PUMP UNIT TO SHUT DOWN DURING HYDRAULIC RATE MODIFICATIONS ON THE PIPELINE. THE CONTROL CENTER RECEIVED ALARMS OF THE UNITS CONTINUING TO RUN. THE CONTROL CENTER SHUT DOWN THE PIPELINE SYSTEM AND CONTACTED FIELD PERSONNEL TO INVESTIGATE. FAILURE OF THE ESD SYSTEM RENDERED THE CONTROL EQUIPMENT NON FUNCTIONAL DUE TO LOSS OF 48 VOLT POWER SYSTEM AND THE BACK UP ENERGY STORAGE DEVICE FAILED TO OPEN POWER CONTACT TO THE MOTOR STARTER OF THE PUMP UNITS, WHICH WOULD HAVE SHUT DOWN THE PUMP MOTOR. BARRIERS HAVE BEEN ADDED TO THE 48 VDC SYSTEM, REVISED THE PLC LOGIC, ADDED FAIL SAFE FEATURES, WILL USE THE SF6 SUB-STATION BREAKER AS A SECONDARY CONTROL BARRIER. PIPELINE RE-STARTED WITH THE PUMP STATION BYPASSED UNTIL REPAIRS WERE COMPLETED. THE PUMP STATION WAS RESTARTED ON JUNE 17TH WITH THE BARRIERS INSTALLED.