EXPLORER PIPELINE CO

hazardous_liquid Incident — — September 20, 2016

Incident Information

Incident DateSeptember 20, 2016
OperatorEXPLORER PIPELINE CO
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates30.84378, -95.49514

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$7,340
Emergency Response$8,396
Other Costs$0

Location Map

Incident Narrative

"ON SEPTEMBER 20, 2016 AT 15:30 EXPLORER PERSONNEL IDENTIFIED A CHECK VALVE EAR ASSOCIATED WITH THE MAINLINE STATION CHECK VALVE THAT WAS LEAKING IN AN ENCLOSED UNDERGROUND VAULT AT THE HUNTSVILLE, TEXAS PUMP STATION. AT THE TIME OF THE EVENT, THE SUCTION SIDE OF THE CHECK VALVE WAS 145 PSIG AND THE DISCHARGE SIDE OF THE CHECK VALVE WAS 293 PSIG. EQUIPMENT WAS DISPATCHED AND REPAIRS WERE MADE TO THE CHECK VALVE ON SEPTEMBER 21, 2016. THE INVESTIGATION INDICATED A BUSHING AND SEAL WERE WORN ON THE CHECK VALVE. THE VALVE WAS ORIGINALLY INSTALLED IN 1973, BUT NO RECORDS REFLECT WHEN THE BUSHING OR SEALS WERE REPLACED. A MULTI YEAR PLAN IS IN REPLACE TO REPLACE THE BUSHINGS AND SEALS ON SIMILAR CHECK VALVES."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in