CENTRAL FLORIDA PIPELINE CORP
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | CENTRAL FLORIDA PIPELINE CORP |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 28.06844, -81.78589 |
Cause
| Cause | NATURAL FORCE DAMAGE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
ON JULY 12, 2015, THE FIRE DEPARTMENT CONTACTED THE HOUSTON CONTROL CENTER REPORTING A LEAK AT THE AUBURNDALE STATION. A RIGHT OF WAY TECHNICIAN WAS DISPATCHED TO AUBURNDALE STATION AND DISCOVERED A MIST OF JET FUEL BEING RELEASED FROM A SECTION OF STAINLESS STEEL TUBING COMING FROM THE 10 INCH PIPELINE LEADING TO A PRESSURE TRANSMITTER. THE RIGHT OF WAY TECHNICIAN ISOLATED THE TUBING AND STOPPED THE RELEASE. THE LEAK WAS THE RESULT OF ARCING BETWEEN THE STAINLESS STEEL TUBING AND STEEL TUBING SUPPORT, WHICH MELTED THE TUBING. LIGHTNING STRUCK AT OR CLOSE TO THIS LOCATION WHICH ALLOWED THE CURRENT TO FLOW ONTO THE THE TUBING TO GROUND.