SEADRIFT PIPELINE CORP

hazardous_liquid Incident — — August 1, 2015

Incident Information

Incident DateAugust 1, 2015
OperatorSEADRIFT PIPELINE CORP
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.84415, -94.91139

Cause

CauseEQUIPMENT FAILURE
SubcauseOTHER EQUIPMENT FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$500
Emergency Response$200
Other Costs$0

Location Map

Incident Narrative

ON AUGUST 1, 2015 AT 2:02 P.M. A FAILURE AT A FLANGE CONNECTION TO A PRESSURE TRANSMITTER OFF OF PROPANE PIPING INSIDE THE WINFREE PUMP STATION RESULTED IN A RELEASE OF 66.7 LBS PROPANE. LEAK DETECTION ALARMS ALERTED HOUSTON PRODUCT CONTROL WHO TOOK ACTION TO ISOLATE THE LEAK. TECHNICIANS IMMEDIATELY RESPONDED AND STOPPED THE LEAK IN 43 MINUTES. ROOT CAUSE WAS DETERMINED BY PIPELINE OPERATIONS THAT A BLIND FLANGE WAS TAPPED AND UTILIZED IN THE INSTALLATION OF THE TRANSMITTER WHERE IT MATES UP WITH THE INSTRUMENT.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in