ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 30.03003, -94.04120 |
Cause
| Cause | INCORRECT OPERATION |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
OPERATORS PERFORMED MAINTENANCE ON THE VERTICAL STRAINER BASKETS ON THE METER SKID AND RETURNED THE SKID TO OPERATION. THE STRAINER'S SAFETY BLEED VALVE PLUG WAS NOT RE-INSTALLED PRIOR TO THE RETURN OF EQUIPMENT TO OPERATION. WHEN A MOVEMENT OF GASOLINE WAS MADE ON THE METER SKID, APPROXIMATELY 57 GALLONS OF GASOLINE WAS RELEASED FROM THE TWO 1/16"" ORIFICES ON THE SAFETY BLEED VALVE. THE PIPELINE WAS THEN SHUT DOWN AND ISOLATED. RELEASED PRODUCT WAS REMEDIATED, THE PLUG REINSTALLED, THE EQUIPMENT LEAK TESTED, AND THE SKID BROUGHT BACK INTO SERVICE. AN EQUIPMENT-SPECIFIC MAINTENANCE PROCEDURE WAS WRITTEN TO PREVENT REOCCURRENCE OF THIS RELEASE.