MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates41.56348, -93.52167

Cause

CauseOTHER ACCIDENT CAUSE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

DURING A ROUTINE INSPECTION OF THE FACILITY, LOCAL MAGELLAN OPERATIONS PERSONNEL IDENTIFIED PRODUCT WEEPING OUT OF A LEAK DETECTION PORT ON TANK 2701. THE TANK WAS A NEW CONSTRUCTION TANK AND HAD BEEN IN SERVICE APPROXIMATELY 5 DAYS. THE TANK WAS EMPTIED, CLEANED AND AN INSPECTION CREW DISCOVERED PINHOLES IN THE FLOOR WELDS ON THE TANK BOTTOM THAT WERE NOT IDENTIFIED DURING CONSTRUCTION. THE PINHOLES WERE REPAIRED IN ACCORDANCE WITH A REMEDIATION PLAN APPROVED BY THE PHMSA CENTRAL REGION. THE TANK WAS RETURNED TO SERVICE JANUARY 27, 2016. APPROXIMATELY 50 CUBIC YARDS OF IMPACTED SOIL WILL BE REMEDIATED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in