"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — May 8, 2017

Incident Information

Incident DateMay 8, 2017
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72536, -95.20334

Cause

CauseCORROSION FAILURE
SubcauseINTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$194,850
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"PRODUCT WAS FOUND ON TOP OF INTERNAL PONTOON ROOF ON TANK 12-30. PRODUCT WAS REMOVED AND TANK WAS EMPTIED TO DETERMINE CAUSE. TANK HAS BEEN CLEANED, AND INITIAL INSPECTION DETERMINED THAT THE LEAK CAME FROM CRACKS IN THE WELD. UPON FURTHER INVESTIGATION, WE DETERMINED THE CAUSE TO BE GENERAL INTERNAL CORROSION RELATED TO THE TRANSMIX PRODUCT. THE INTERNAL FLOATING ROOF WAS REPLACED. TO PREVENT THE RE-OCCURRENCE, WE HAVE COATED THE UNDERSIDE OF THE ROOF PER NACE GUIDELINES."