SUNOCO PIPELINE L.P.

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSUNOCO PIPELINE L.P.
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates39.86530, -75.13790

Cause

CauseNATURAL FORCE DAMAGE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

WHILE PERFORMING A DAILY INSPECTION, A SXL OPERATOR OBSERVED A DIESEL RELEASE FROM PIPING IN THE TANK 401 DIKE AREA. VISUAL INVESTIGATION DETERMINED THE SOURCE AS A SLOW TRICKLE FROM A 3"" GATE VALVE AT THE STEM/BONNET. PLANT SUPERVISION WAS NOTIFIED. OSRO'S WERE CALLED TO RESPOND TO THE RELEASE. APPROXIMATELY 58 GALLONS WAS RELEASED AND RECOVERED. THE IMPACTED SOIL WAS REMOVED. SUBSEQUENT INVESTIGATION DETERMINED THAT THE 3"" GATE VALVE LOCATED AT THE END OF THE PIPE RUN HAD RETAINED WATER, FROZE AND EXERTED FORCE ON THE PACKING/BONNET WHICH ALLOWED THE DIESEL TO LEAK. THE VALVE WAS REMOVED AND THE LINE BLINDED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in