ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates30.00887, -94.05426

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

TERMINAL OPERATOR IDENTIFIED CRUDE OIL ON GROUND BELOW TANK PIPING CROSSOVER RACK IN THE BEAUMONT CRUDE TERMINAL. THE TANK RECIRCULATION PIPING WAS BEING COMMISSIONED AT THE TIME OF LEAK IDENTIFICATION. THE LEAK WAS DETERMINED TO BE AT A FLANGED CONNECTION BETWEEN RECIRCULATION PIPING AND A 16-INCH VALVE. INSPECTION OF THE CONNECTION INDICATED BOLTS WERE IMPROPERLY RE-TIGHTENED FOLLOWING REMOVAL OF A BLIND DURING HYDROTESTING OF THE NEWLY-INSTALLED PIPING. ALL FLANGE BOLTS WERE RE-TORQUED TO ENTERPRISE SPECIFICATIONS TO STOP THE LEAK. IMPACTED SOIL WAS REMOVED BY QUALIFIED CONTRACTORS. OPERATIONS THROUGH THE IMPACTED FLANGE WERE RESUMED AND NO FURTHER LEAKS WERE DETECTED.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in