DCP MIDSTREAM

hazardous_liquid Incident — — July 29, 2017

Incident Information

Incident DateJuly 29, 2017
OperatorDCP MIDSTREAM
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates28.55871, -98.16352

Cause

CauseEQUIPMENT FAILURE
SubcauseTHREADED CONNECTION/COUPLING FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$50
Emergency Response$0
Other Costs$3,875

Location Map

Incident Narrative

"A SMALL FROST BALL FOUND ON SCREWED FITTING AROUND PUMP 2 SUCTION BYPASS VALVE. CRACK WAS FOUND IN THE THREADS OF THE NIPPLE. THREADS WERE CUT OFF AND NIPPLE RETHREADED AND BYPASS REPLUMBED. LOST 5 GALLONS OF PRODUCT AND FLARED 123 BARRELS TO MAKE REPAIRS. TO PREVENT RECURRENCE, PUMP 2 WAS REPLACED WITH A NEWLY OVERHAULED PUMP TO REDUCE VIBRATION AND NOW VIBRATION IS MINIMAL."