"BUCKEYE PARTNERS, LP"

hazardous_liquid Incident — — August 24, 2017

Incident Information

Incident DateAugust 24, 2017
Operator"BUCKEYE PARTNERS, LP"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates40.61249, -74.24019

Cause

CauseMATERIAL FAILURE OF PIPE OR WELD
Subcause"DESIGN-, CONSTRUCTION-, INSTALLATION-, OR FABRICATION-RELATED"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$80,000
Emergency Response$500
Other Costs$0

Location Map

Incident Narrative

"ON 8/24/17 A DELIVERY INTO T151 BEGAN. AT APPROXIMATELY 1415 HOURS MINOR STAINING WAS RECOGNIZED ALONG THE DRAIN PIPE AND WAS INVESTIGATED BUT NO ISSUES WERE IDENTIFIED. ON 8/25/17 THE TANK WAS EMPTIED. DURING THIS ACTIVITY THE DRAIN VALVE BETWEEN FLOORS WAS CHECKED AND FREE PRODUCT WAS DISCOVERED IN THE SUMP PIPING BETWEEN THE DOUBLE BOTTOM FLOOR IN THE CENTER SUMP. ON 8/25/2017 AT APPROXIMATELY AT 1735 HOURS THE NRC WAS NOTIFIED. A VACUUM TRUCK WAS BROUGHT IN TO EVACUATE THE PIPING. THE LINDEN FIRE DEPARTMENT WAS NOTIFIED AND ARRIVED ON SITE TO ENSURE THERE WERE NO EXTERNAL RELEASE. THE LINDEN FIRE DEPARTMENT INSPECTED AND CONFIRMED NO PRODUCT WAS OUTSIDE CONTAINMENT. THERE WAS NO IMPACT TO THE ENVIRONMENT, NO INJURIES, NO EXPOSURES, NO FIRES. SINCE DISCOVERY, THE TANK HAS BEEN EVACUATED, VISUALLY INSPECTED AND CLEANED. ABRASIVE BLAST WAS PERFORMED TO ALL FLOOR WELDS AND THE ENTIRE SUMP, NOTHING OF SIGNIFICANCE WAS FOUND. A HELIUM TEST WAS PERFORMED, A MAG PARTICLE TEST WAS PERFORMED AND A 2ND HELIUM TEST WAS PERFORMED. NOTHING OF SIGNIFICANCE HAS BEEN FOUND. SINCE OCTOBER 1ST A PRESSURE TEST WAS CONDUCTED, A SECOND HELIUM TEST WAS PERFORMED. THE TANK WAS FILLED WITH WATER AND HELD PRESSURE FOR THREE DAYS WITH NO LOSS. THROUGH ABRASIVE BLAST TESTING A CRACK GUSSET WELD WAS VISUALLY DISCOVERED IN THE TANKS CENTER SUMP. ALSO IDENTIFIED THROUGH VISUAL EXAMINATION WERE THREE PINHOLES ON THE BELLMOUTH TO SUMP CORNER WELD. THE PINHOLES MANIFESTED THEMSELVES THROUGH PRODUCT STAINING. FOLLOWING ALL REPAIRS A FULL HYDROTEST WAS SUCCESSFULLY COMPLETED ON TANK 151. NO ADDITIONAL TESTING IS REQUIRED IN THIS INCIDENT."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in