WEST TEXAS GULF PIPELINE CO

hazardous_liquid Incident — — June 6, 2016

Incident Information

Incident DateJune 6, 2016
OperatorWEST TEXAS GULF PIPELINE CO
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates32.15284, -97.37462

Cause

CauseCORROSION FAILURE
SubcauseINTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$26,761
Emergency Response$83,283
Other Costs$0

Location Map

Incident Narrative

ON 06/06/2016 COMPANY PERSONNEL ARRIVED AT BLUM STATION AT APPROXIMATELY 07:00 AND DISCOVERED CRUDE OIL IN THE CONTAINMENT AREA. THE CONTROL CENTER WAS IMMEDIATELY NOTIFIED AND THE MAINLINE WAS SHT DOWN. EMERGENCY RESPONSE PERSONNEL WERE ACTIVATED AND DISPATCHED TO THE SITE. APPROXIMATELY 200 BARRELS WERE RELEASED TO THE CONTAINMENT AREA AND FACILITY RETENTION POND. INVESTIGATION REVEALED A PINHOLE IN A 4"" DRAIN LINE FROM THE BOTTOM OF THE STRAINER BASKET TO THE SUMP. THE AFFECTED PIPING WAS REMOVED AND ASSOCIATED PIPING/APPURTENANCES WERE BLINDED. THE FAILED PIPE WAS SENT FOR METALLURGICAL ANALYSIS AND IT WAS DETERMINED THAT THE CAUSE WAS MICROBIAL INDUCED, INTERNAL CORROSION. NEW STRAINER PIPING INSTALLED WILL HAVE AN INTERNAL LINER TO PREVENT RECURRENCE OF INTERNAL CORROSION AND FUTURE RELEASES.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in