ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — October 24, 2017

Incident Information

Incident DateOctober 24, 2017
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.60429, -95.13122

Cause

CauseINCORRECT OPERATION
SubcauseEQUIPMENT NOT INSTALLED PROPERLY

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,800
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"THE PIPELINE HAD BEEN SHUTDOWN AND PURGED WITH NITROGEN FOR MAINTENANCE. AFTER MAINTENANCE HAD BEEN PERFORMED, A SPOOL PIECE THAT HAD BEEN REMOVED TO HELP DRY THE PIPELINE WAS REINSTALLED ON 10/22/2017. THE FOLLOWING DAY, 10/23/2017, A LEAK TEST UTILIZING NITROGEN WAS PERFORMED ON THE ENTIRE PIPELINE. THE LINE PASSED THE 200 PSIG LEAK TEST. ON 10/24/2017 OPERATIONS BEGAN COMMISSIONING THE PIPELINE AND AT 23:17 A TECHNICIAN OBSERVED A GASKET LEAK AT THE TENNECO VALVE SITE. ON 10/25/2017 AT 0142 IT WAS DETERMINED THE VOLUME OF PRODUCT EXCEEDED 5 GALLONS AND, ALTHOUGH THE EVENT DID NOT MEET NRC REPORTING CRITERIA, THE TRRC WAS NOTIFIED AT 0200. IT WAS FOUND THAT THE FLANGES WERE MISALIGNED AND THE BOLTS WERE NOT PROPERLY TORQUED RESULTING IN A LEAK AROUND THE GASKET. THE GASKET WAS REPLACED AND THE FLANGE WAS PROPERLY ALIGNED AND TORQUED."