VITOL MIDSTREAM, LLC

hazardous_liquid Incident — — July 6, 2016

Incident Information

Incident DateJuly 6, 2016
OperatorVITOL MIDSTREAM, LLC
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates31.94442, -101.92234

Cause

CauseINCORRECT OPERATION
SubcauseTANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$1,000
Other Costs$0

Location Map

Incident Narrative

AT APPROXIMATELY 09:55 HRS TO 09:58 HRS ON 07/06/2016 THE VITOL MIDLAND TANK FARM TANK HEADER SUMP FILLED UP WITH CRUDE OIL CAUSING AN OIL MIST TO COME OUT OF THE SUMP VENT AND OIL LIQUID TO FLOW OUT OF SUMP DRAINS ON TRANSFER PUMPS # 1 & # 2 BECAUSE THE RELIEF VALVE (SET @ 310PSI) ON THE 12 INCH VM 1 PIPELINE OPENED TO THE DRAIN SYSTEM AND RAPIDLY FILLED THE UNDERGROUND SUMP CAUSING IT TO OVERFLOW. THE RELIEF VALVE WAS ACTIVATED WHEN PRESSURE BUILT UP ON THE VM 1 PIPELINE AS A RESULT OF THE HWY I-20 TRUCK STATION PD PUMP(S) TURNING ON AUTOMATICALLY (DUE TO TANK LEVEL) AND PUMPING AGAINST CLOSED VALVES MOV006, MOV31102, AND MOV23201 AT THE VITOL MIDLAND TANK FARM AND CLOSED VALVE MOV920 AT ENTERPRISE. PROCEDURE FOR THIS OPERATION WAS DEVELOPED AND PERSONNEL TRAINED TO PREVENT RECURRENCE.